Medical Gas Verifiers / Certifiers (ASSE 6030 or NFPA 99C certified)
Company Overview
GD Resources LLC is seeking a qualified contractor to provide Annual Medical Gas Testing, Certification, and Master Alarm Testing Services at the Phoenix VA Medical Center campus. This contract will support compliance with applicable engineering policies and safety standards governing medical gas systems in healthcare facilities.
This requirement is a construction-related service activity and does not involve access to VA sensitive information or a security accreditation package.
Project Overview
The selected contractor will perform annual testing, inspection, certification, and documentation of the Medical Gas systems and Master Alarm panels located throughout the Phoenix VA Medical Center campus.
All testing and certification activities must comply with:
Engineering Policy Memorandum No. FS/138-1027
NFPA 99C Medical Gas Systems Standards
CGA G7.1 ANSI Grade “N” Air Standards
Applicable manufacturer recommendations and safety guidelines.
The Medical Gas systems covered include:
Oxygen
Medical Air
Medical Vacuum
Waste Anesthesia Vacuum
Nitrous Oxide
Dental Air
Dental Vacuum
Critical components to be tested and inspected include:
Bulk Oxygen tanks
Medical Vacuum systems
Medical Air systems
Waste Anesthesia Vacuum systems
Oxygen and Nitrous Oxide H-tank supply manifolds
Master alarm signal panels
Area alarms
Automatic pressure switches
Shutoff valves
Flexible connectors
Medical gas outlets and inlets
Contractor Qualifications
The Prime Contractor must:
Have completed NFPA 99C Medical Gas Certifier training
Provide current certification of qualifications
Utilize certified and calibrated testing equipment
Employ certified inspectors trained in Medical Gas testing and certification
Provide documentation of all personnel certifications to the Contracting Officer Representative (COR) prior to work commencement.
Scope of Work and Responsibilities
Medical Gas Outlet Testing
The contractor shall test 100% of Medical Gas outlets and inlets in the following buildings:
Building 1 – Phoenix VA Medical Center (Main Building)
Building 8 – Ambulatory Care Center
Building 16 – Community Living Center
Building 29 – Dental Clinic
Testing activities shall include:
Flow rate verification at each outlet
Static pressure measurement
Purity testing for Oxygen, Medical Air, and Nitrous Oxide
Suspended particulate testing
Leak detection
Visual inspection for damage
Minimum performance standards include:
Oxygen, Medical Air, Nitrous Oxide: ≥100 LPM flow
Surgical outlets: ≥142 LPM flow
Medical Vacuum outlets: ≥85 LPM flow
Static pressure: 50–55 PSI
Medical Vacuum: minimum 12 inches Hg
Oxygen and Nitrous Oxide purity: ≥99%
Medical Air Quality Testing
Medical Air outlets and compressors must conform to CGA G7.1 ANSI Grade “N” Air Standards, including testing for:
Carbon dioxide
Sulfur
Nitrous fumes
Carbon monoxide
Oil concentration
Dew point
System Component Inspections
The contractor shall inspect and test:
Flexible connectors
Nonstationary booms and articulating assemblies
Zone, riser, source, and mainline valves
Oxygen bulk tank set points
Leak detection at all applicable joints and outlets
Alarm Panel Testing
Annual operational testing shall be conducted for Medical Alarm Panels located at:
H117 – Graphic Room (Boiler Plant)
H107 – Maintenance Supervisor Office
E100A – Operators Room
Medical Gas System Inventory
The contractor shall verify and maintain the medical gas inventory for all covered buildings.
Building 1 – Main Building
Valves: 216
Area Alarm Signals: 101
Master Alarm Signals: 60
Outlets/Inlets: 1,698
Building 8 – Ambulatory Care Center
Valves: 44
Area Alarm Signals: 41
Master Alarm Signals: 69
Outlets/Inlets: 105
Building 29 – Dental Clinic
Valves: 13
Area Alarm Signals: 11
Master Alarm Signals: 10
Outlets/Inlets: 53
Deliverables and Documentation
The contractor shall provide:
Medical Gas Campus Overview Book within 30 days of the initial site visit
Annual updated Medical Gas Overview Book
Calibration documentation for carbon dioxide and dew point meters
Electronic inspection report within 10 working days
Detailed discrepancy report including explanations and proposed corrective actions
Reports must be submitted electronically to:
Contracting Officer
Maintenance Shop Supervisor
Maintenance and Operations Supervisor
General Requirements
Provide two weeks advance notification prior to site visits to the Engineering authority.
Maintain all inspection and testing records in accordance with VA and NFPA standards.
Ensure all testing and certification work is conducted by qualified and certified personnel.
Equal Opportunity Statement
GD Resources LLC is an Equal Opportunity Employer. We are committed to fostering a diverse and inclusive workplace and do not discriminate on the basis of race, color, religion, sex, national origin, age, disability, veteran status, or any other protected status under applicable federal, state, or local laws